Part details:
GE-MK6eS IS200TREGS1B
GE documentation identifies this revision as providing 3 monitored trip relay outputs when used with the YPROS1A I/O pack. TREG is documented as working as a board pair with TRPG: power for trip solenoids passes into TRPG through its J1 connector, then is conducted to TREG over a J2 cable. TREG also includes a JH1 power input connector that supplies contact wetting voltage to up to seven optional trip interlock contacts. The hardware uses a box-style terminal block. It should be matched with the compatible TRPG terminal board where that pairing is used in the site configuration.
This component is typically considered when troubleshooting Mark VIeS Safety hardware, replacing a failed module, evaluating repair options, or maintaining spare inventory for turbine protection systems. Before installation, verify the catalog number, hardware revision, and associated terminal board or I/O pack configuration against site documentation and OEM requirements. The OEM reference for this listing is GEH-6721 Vol I; GEH-6721 Vol II.
Control system parts are provided by GTC Control Solutions, Inc., a wholly owned subsidiary of B7B. Parts are offered in unused, repaired, or remanufactured condition, subject to availability. Each repaired or remanufactured component undergoes comprehensive functional testing in energized panels to guarantee reliability and performance. We provide detailed test reports and warranties with every repair, giving you confidence in the quality and longevity of your replacement parts.
Specifications
- Part number
- IS200TREGS1B
- Model
- GE-MK6eS
- OEM
- General Electric
- Classification
- Protection & Safety
- Control System / Platform
- GE Mark VIeS
- Module Type / Function
- TREG Emergency Trip Gas Terminal Board
- I/O Category
- Discrete / Protection I/O
- Channel / Point Count
- 3 monitored trip relay outputs
- Signal Type / Electrical Interface
- Emergency gas turbine trip protection signals
- Power Requirements
- Trip solenoid/contact wetting power supplied through TRPG/TREG pair
- Primary Connectors / Termination Style
- box-style terminal block
- Form Factor / Mounting
- Safety trip terminal board
- System Architecture / Redundancy Support
- 3-pack emergency protection configuration where documented
- Associated / Compatible Boards
- TRPG terminal board; YPROS1A I/O pack
- OEM Manual Reference
- GEH-6721 Vol I; GEH-6721 Vol II