GE-MK6E IS200TRLYH1F
GE documentation identifies the supported point or channel information as 36 mechanical relays; 12 voted Form A normally open outputs. The electrical or signal interface is documented as 115 Vac, 24/48/125 V dc relay output circuits. The hardware uses a T-type barrier terminal board form factor. The system architecture should be matched to the documented configuration, including TMR only for TRLY_1F/2F. It should be matched with compatible hardware such as PDOA I/O pack; WPDF option board where applicable where that pairing is used in the site configuration.
This component is typically considered when troubleshooting Mark VIe hardware, replacing a failed module, evaluating repair options, or maintaining spare inventory for turbine control systems. Before installation, verify the catalog number, hardware revision, and associated terminal board or I/O pack configuration against site documentation and OEM requirements. The OEM reference for this listing is GEH-6721 Vol I; GEH-6721 Vol II.
Control system parts are provided by GTC Control Solutions, Inc., a wholly owned subsidiary of B7B. Parts are offered in unused, repaired, or remanufactured condition, subject to availability. Each repaired or remanufactured component undergoes comprehensive functional testing in energized panels to guarantee reliability and performance. We provide detailed test reports and warranties with every repair, giving you confidence in the quality and longevity of your replacement parts.
Specifications
- Part number
- IS200TRLYH1F
- Model
- GE-MK6E
- OEM
- General Electric
- Classification
- Terminal Boards
- Control System / Platform
- GE Mark VIe
- Module Type / Function
- TRLY Relay Output Terminal Board
- I/O Category
- Discrete / Protection I/O
- Channel / Point Count
- 36 mechanical relays; 12 voted Form A normally open outputs
- Signal Type / Electrical Interface
- 115 Vac, 24/48/125 V dc relay output circuits
- Power Requirements
- Field supply depends on board revision and relay application
- Primary Connectors / Termination Style
- Barrier terminal blocks; JA1 for simplex and JR1/JS1/JT1 for TMR on applicable boards
- Form Factor / Mounting
- T-type barrier terminal board form factor
- System Architecture / Redundancy Support
- TMR only for TRLY_1F/2F
- Associated / Compatible Boards
- PDOA I/O pack; WPDF option board
- OEM Manual Reference
- GEH-6721 Vol I; GEH-6721 Vol II
- Warranty
- Unused:
- 2 years
- Repaired:
- 2 years
- Remanufactured:
- 3 years