GE-MK6E IS200TTURH1B

The General Electric IS200TTURH1B (TTUR) is a Primary Turbine Protection Input terminal board for GE SPEEDTRONIC™ Mark VI turbine control systems, working with the IS200VTUR board. It supports 12 passive pulse-rate devices sensing a toothed wheel to measure turbine speed, generator and bus voltage signals from potential transformers, a 125 V dc output to the main breaker coil for automatic generator synchronizing, and inputs from shaft voltage/current sensors.

TTUR includes three relays (K25, K25P, K25A) that must all close to energize the main breaker (52G). The speed-signal cable to VTUR uses the JR5 connector, and other signals use JR1; in TMR systems, signals fan out to JR5/JS5/JT5 and JR1/JS1/JT1. Note: TTURH1B does not support Mark VIe I/O packs.

For maintenance and procurement teams, IS200TTURH1B should be matched to the existing VTUR board and redundancy configuration per GEH-6421 Volume II before ordering a replacement.

Control system parts are provided by GTC Control Solutions, Inc., a wholly owned subsidiary of B7B. Parts are offered in unused, repaired, or remanufactured condition, subject to availability. Each repaired or remanufactured component undergoes functional testing in energized panels, with test reporting and warranty support provided for repair and lifecycle-extension programs.

Specifications

Part number
IS200TTURH1B
Model
GE-MK6E
OEM
General Electric
Classification
Primary Turbine Protection Input Terminal Board
Manufacturer
General Electric
Control System / Platform
GE Mark VI
Series / Family
GE SPEEDTRONIC™ Mark VI
Module Type / Function
TTUR
I/O Category
Turbine Protection Input
Channel / Point Count
12 passive pulse rate speed inputs plus generator/bus voltage, shaft voltage/current, and breaker interface signals
Signal Type / Electrical Interface
Magnetic speed pickup, PT voltage, shaft voltage/current, and breaker relay interface
Network / Communications Interface
Cabled interface to VTUR
Power Requirements
125 V dc breaker-close power path and 28 V dc relay interface as shown in TTUR circuitry
Primary Connectors / Termination Style
Two 24-point terminal blocks plus JR5/JS5/JT5 and JR1/JS1/JT1 connectors
Form Factor / Mounting
Panel-mounted terminal board
System Architecture / Redundancy Support
Simplex and TMR
Associated / Compatible Boards
VTUR primary turbine protection board; TRPG trip board
OEM Manual Reference