Part details:
GE-MK6e IS200TVBAH2A
GE documentation identifies TVBA as a signal interface board for the Mark VIe PVIB I/O pack, providing a direct vibration interface to Eddy-current (position and velocity), seismic, Velomitor, and accelerometer sensors, as well as a dynamic pressure interface to charge amplifiers. This revision, TVBAH2A, is documented as compatible with the PVIBH1A and PVIBH1B I/O packs and includes buffered output circuits with DIN and BNC connectors; it is not IEC 61508 safety-certified and allows mixing of I/O pack revisions. The terminal board accepts 14 sensor inputs on two 24-point terminal blocks and requires the WNPS negative power supply daughterboard to generate the -28 V dc needed for sensor power.
This component is typically considered when troubleshooting Mark VIe hardware, replacing a failed module, evaluating repair options, or maintaining spare inventory for turbine control systems. Before installation, verify the catalog number, hardware revision, and associated terminal board or I/O pack configuration against site documentation and OEM requirements. The OEM reference for this listing is GEH-6721 Vol I; GEH-6721 Vol II.
Control system parts are provided by GTC Control Solutions, Inc., a wholly owned subsidiary of B7B. Parts are offered in unused, repaired, or remanufactured condition, subject to availability. Each repaired or remanufactured component undergoes comprehensive functional testing in energized panels to guarantee reliability and performance. We provide detailed test reports and warranties with every repair, giving you confidence in the quality and longevity of your replacement parts.
Specifications
- Part number
- IS200TVBAH2A
- Model
- GE-MK6e
- OEM
- General Electric
- Classification
- Turbine Control Modules
- Control System / Platform
- GE Mark VIe
- Module Type / Function
- TVBA Vibration Terminal Board
- I/O Category
- Vibration Monitoring I/O
- Channel / Point Count
- 14 sensor inputs on two 24-point terminal blocks and requires the WNPS negative power supply daughterboard to generate the -28 V dc needed for sensor power
- Signal Type / Electrical Interface
- Eddy-current, seismic, Velomitor, accelerometer, and dynamic pressure inputs
- Power Requirements
- -28 V dc sensor power via WNPS or integrated supply where applicable
- Primary Connectors / Termination Style
- Two 24-point terminal blocks; DIN/BNC buffered outputs on equipped revisions
- Form Factor / Mounting
- Vibration terminal board
- System Architecture / Redundancy Support
- Simplex or TMR depending on pack count and board revision
- Associated / Compatible Boards
- PVIB/YVIB I/O packs; WNPS where required
- OEM Manual Reference
- GEH-6721 Vol I; GEH-6721 Vol II